General | |||||||||||
Topology | On-line double conversion with Power Factor Correction (PFC) system | ||||||||||
Configuration | Rack/Tower | ||||||||||
Part Number | 9PX2000iRTAU | ||||||||||
Rating (VA/Watts) | 2000/1800 | ||||||||||
Dimensions (H x W x D, mm) | 86.5 x 440 x605 | ||||||||||
Weight (kg) | 27.4 | ||||||||||
Warranty | 3 years electronics, 2 years battery | ||||||||||
Electrical Input | |||||||||||
Connection | (1) IEC-320-C14 | ||||||||||
Input Voltage Range | 176-276V without derating (up to 100-276V with derating) | ||||||||||
Nominal Voltage | 200/208/220/230/240V | ||||||||||
Frequency | 50/60 Hz autoselection | ||||||||||
Frequency Range | 40-70 Hz | ||||||||||
Electrical Output | |||||||||||
Nominal Voltage | 200/208/220/230/240V | ||||||||||
Output Receptacles | (6) IEC-320-C13 (2) Aust. 10A | ||||||||||
Remotely controlled sockets | 2 Groups: (2) Aust. 10A & (2) IEC C13 10A | ||||||||||
Efficiency (Normal Mode) | Up to 93% in online mode (Up to 98% in Hi-efficiency mode) | ||||||||||
Output Frequency | 50/60 Hz autoselect, frequency converter mode | ||||||||||
Battery | |||||||||||
Runtime (Minutes) 250 500 750 1000 1250 1500 1750 0 500 1000 1500 2000 2500 3000
Load (Watts) Battery runtimes are approximate and may vary with equipment, configuration, battery age, temperature, etc. Show: Load (Watts): 1759 Standard Runtime: 4 With 1 EBM: 30 With 2 EBMs: 58 With 3 EBMs: 89 With 4 EBMs: 121 | |||||||||||
Battery Management | ABM® & Temperature compensated charging method (user selectable), Automatic battery test, deep discharge protection, automatic recognition of external battery units | ||||||||||
Extended Battery Capability | EBM (2U) | ||||||||||
Communications | |||||||||||
User Interface | Multilingual graphical LCD display | ||||||||||
Communication Ports | 1 USB port + 1 serial RS232 port + 1 mini-terminal block for remote ON/OFF + 1 mini-terminal block for Remote Power Off + 1 mini-terminal block for Output relay | ||||||||||
Communications Slot | 1 slot for Network-MS card, ModBus-MS or Relay-MS cards | ||||||||||
Environmental & Standards | |||||||||||
Audible Noise | 40dB | ||||||||||
Operating Temperature | 0 to 40°C | ||||||||||
Safety markings | IEC/EN 62040-1, UL 1778, CSA 22.2 | ||||||||||
EMC Markings | IEC/EN 62040 -2 , FCC Class B, CISPR22 Class B | ||||||||||
Approvals | CE /CB report (TUV) / cULus / EAC / RCM / KC / Energy Star |