General | |
Topology | On-line double conversion with automatic by-pass and power factor correction |
Configuration | Rack/Tower |
Part Number | M68184 |
Color | metallic grey |
Rating (VA/Watts) | 1500/1350 Maximum rating with EXB battery units: 1200 W |
Dimensions (H x W x D, mm) | 86.5 x 438 x 483 |
Weight (kg) | 20.5 |
Warranty | 2 years warranty, Standard product exchange, including the battery |
Rail Kit Included | Yes |
Electrical Input | |
Connection | (1) IEC-320-C14 |
Input Voltage Without Using Batteries | 100/120/140/160 V to 284V Lower limits for <20%, <33%, <66%, >=66% of nominal power (VA). For active output power greater than 0.7 and 0.8 nominal rating, the lower limit is 180V and 190V respectively |
Input frequency Range Without Using Batteries | 40 to 70 Hz |
Electrical Output | |
Voltages | 230 V (adjustable to 200/208/220/240/250 V), |
Output Receptacles | (6) IEC-320-C13 |
Remotely controlled sockets | 2 independent groups: 2 + 1 IEC C13 (10A) sockets |
Output Frequency | 50/60 Hz auto-select or frequency converter mode (derated by 15% when used as a frequency converter) |
User Interface | (3) LEDs + adjustable multilingual display: display of measurements, access to control and setup menus |
Communication Ports | 1 USB port + 1 RS232 serial port and relay contacts (USB and RS232 serial ports cannot be used simultaneously) 1 mini terminal block for remote ON/OFF and emergency stop |
Communications Card Slots | 1 slot for NMC Minislot card or NMC ModBus/JBus or MC Contacts/Serial |
Environmental & Standards | |
Audible Noise | 45 dBA |
Operating Temperature | 0°C to 40°C continuous |
Performance - Safety - EMC | IEC/EN 62 040-3 (VFI-SS-113), IEC/EN 62 040-1-1, IEC/EN 60 950-1 (RD), IEC/EN 62 040-2 C1 Class |
Approvals | CE, TüV GS, CB report, cTüV-US |